By: Eric Lai, Computerworld(May 14, 2008 06:00:00)

Microsoft Corp.'s plan to fill its mammoth Chicago data centre with servers housed in 40-foot shipping containers has experts wondering whether the strategy will succeed. In Microsoft's plan, each container in the data centre, still being built, will be filled with several thousand servers.

Computerworld queried several outside experts - including the president of a data centre construction firm, a data centre engineer-turned-CIO, an operations executive for a data centre operator and a "green" data centre consultant - to get their assessments of the strategy. While they were individually impressed with some parts of Microsoft's plan, they also expressed skepticism that the idea will work in the long term.

Here are some of their objections, along with the responses of Mike Manos, Microsoft's senior director of data centre services. Manos talked with Computerworld in an interview after the Data Centre World show at which Microsoft's plan was announced.

1. Russian-doll-like nesting (servers, on racks, inside shipping containers) may work out to less Lego-style modularity, as some proponents claim, and more mere...moreness.
Server-filled containers are "nothing more than a bucket of power with a certain amount of CPU capacity," quipped Manos.

His point is that setting up several thousand servers inside a container in some off-site factory setting will make them nearly plug-and-play once the container arrives at the data centre. By shifting the setup to the server vendor or system integrator and then wrapping it up inside a 40-foot metal box, containers become far easier and faster to deploy than individual server racks, which have to be moved one at a time.

But people like Peter Baker, vice president for information systems and IT at Emcor Facilities Services, argue that in other ways, containers still "add complexity."

"This is simply building infrastructure on top of infrastructure," he said.

One example, says Baker - who worked for many years as an electrical engineer building power systems for data centres before shifting over to IT management - is in the area of power management. Each container, he says, will need to come with some sort of UPS (uninterruptible power supply) that does three things: 1) converts the incoming high-voltage into lower usable DC voltages; 2) cleans up the power to prevent it from spiking and damaging the servers; 3) provides backup power in case of an outage.

The problem is that each UPS, in the process of "conditioning" the power, also creates "harmonics" that bounce back up the supply line and can "crap up power for everyone else," Baker said.

Harmonics is a well-known issue that's been managed in other contexts, so Baker isn't saying the problem is unsolvable. But, he argues, the extra infrastructure needed to alleviate the harmonics generated by 220 UPSs - the number of containers Microsoft thinks it can fit inside the Chicago data centre - could easily negate the potential ROI from using containers.

Manos' rebuttal: "The harmonics challenges have long been solved [by Microsoft's] very smart electrical and mechanical folks," he said, though he declined to go into specifics. Manos added that he also "challenged the assumption" that Microsoft's solutions are bulky and non-cost-effective: "You can be certain that we have explored ROI and costs on this size of investment." He also admonished critics' speculation that relies too heavily on the "traditional way of thinking about data centres," again, without going into detail.

2. Containers are not as plug-and-play as they seem.

Servers normally get shipped from factory to customer in big cardboard boxes, protected by copious Styrofoam. Setting them up on vibration-prone racks before they travel cross-country by truck is a recipe for broken servers, argues Mark Svenkeson, president of Hypertect Inc., a Roseville, Minn., builder of data centres. At the very least, "verifying the functionality of these systems when they arrive is going to be a huge issue."

But damaged servers haven't been a problem, claimed Manos, since Microsoft began deploying containers at its data centres a year ago.

"Out of tens of deployments, the most servers we've had come DOA is two," he said. Manos also downplayed the labor of testing and verifying each server. "We can know pretty quick if the boxes are up and running with a minimum of people," he said.

He also pointed out that Microsoft plans to make its suppliers liable for any transit-related damage.

So let's say Microsoft really has solved this issue of transporting server-filled containers. But part of what makes the containers so plug-and-play is that they will, more or less, sport a single plug from the container to the "wall" for power, cooling, networking and so forth.

But, Svenkeson pointed out, that also means that an accident such as a kicked cord or severed cable would result in the failure of several thousand servers, not several dozen. It's like those server rooms that go dark because somebody flicks the uncovered emergency "off" switch out of curiosity or spite.

"If you're plugging all of the communications and power into a container at one point, then you've just identified two single points of failure in the system," Svenkeson said.

While Manos conceded the general point, he also argued that a lot "depends on how you architect the infrastructure inside the container."

Outside the container, Microsoft is locating services worldwide - similar to Google's infrastructure - in order to make them redundant in case of failure. In other words, users accessing a hosted Microsoft application, including Hotmail, Dynamics CRM or Windows Live, may connect to any of the company's data centres worldwide.

That means that "even if I lose a whole data centre, I've still got nine others," Manos said. "So I'll just be at 90 per cent serving capacity, not down hard."

Microsoft is so confident its plan will work that it's installing diesel generators in Chicago to provide enough electricity to back up only some, not all, of its servers.

Few data centres dare to make that choice, said Jeff Biggs, senior vice president of operations and engineering for data centre operator Peak 10 Inc., despite the average North American power uptime of 99.98 per cent.

"That works out to be about 17 seconds a day," said Biggs, who oversees 12 data centres in southeastern states. "The problem is that you don't get to pick those 17 seconds."

3. Containers leave you less, not more, agile.

Once containers are up and running, Microsoft's system administrators may never go inside them again, even to do a simple hardware fix. Microsoft's research shows that 20 per centB to 50 per centB of system outages are caused by human error. So rather than attempt to fix malfunctioning servers, it's better to let them die off.

To keep sysadmins from being tempted to tinker with dying servers, Microsoft plans to keep its Chicago IT staff to a total of 35. With multiple shifts, that works out to fewer than 10 techs on-site at any given time. That's despite the 440,000 or more servers Microsoft envisions scattering across the equivalent of 12 acres of floor space.

But where Manos sees lean and mean, others envision potential disaster.

"It seems pretty thin to me," said Svenkeson, who has been building data centres for 20 years. "These are complex systems to operate. To watch them remotely and do a good job of it is not cheap."

As more and more servers go bad inside the container, Microsoft plans to simply ship the entire container back to the supplier for a replacement.

It becomes a problem, then, of defining the tipping point. As more servers die, the opportunity cost of not replacing the container grows bigger and bigger.

"Say 25 per centB of the servers have failed inside a container after a year. You may say you don't need that compute capacity - fine," said Dave Ohara, a data centre consultant and blogger. "But what's potentially expensive is that 25% of the power committed to that container is doing nothing. Ideally, you want to use that power for something else.

"Electrical power is my scarce resource, not processing power," Ohara concluded.

Biggs agreed. "Intel is trying to get more and more power efficient with their chips," Biggs said. "And we'll be switching to solid-state drives for servers in a couple of years. That's going to change the power paradigm altogether."

But replacing a container after a year or two when a fraction of the servers are actually broken "doesn't seem to be a real green approach, when diesel costs $3.70 a gallon," Svenkeson said.

Manos acknowledged that power is somewhat "hard-wired" within the data centre, making it difficult to redistribute. But he asserted that if a data centre is "architected smartly on the backside, you can get around on those challenges, by optimizing your power components and your overall design." He declined to elaborate.

If containers need to be swapped out before expectation, that cost will be borne by the container vendor, not Microsoft, said Manos.

But he hinted that Microsoft is willing to tolerate a fairly large opportunity cost - that is, hold onto containers even if a large percentage of the servers have failed and are taking up valuable power and real estate as a result. "I don't know too many people who are depreciating server gear over 18 months. Rather, I see pressure to move out to a five-to-six-year cycle."

Next page:Containers don't make a data centre greener

Bookmark on:del.icio.us| Digg it| Furl| Google| Technorati| StumbleIt| Yahoo!

Have something to say about this article?
Add a new commentLetter to the Editor
Find an inappropriate comment? You can notify the moderator by clicking the Report an innapropriate comment icon.
ADD A COMMENT
Name:*Your email address will not appear online and will be used only in the event that the editor wishes to contact you personally for additional comment.
City:
Email:
Title:*
Comment:*
* required fields
Blog Spotlight: Sandford Borins
Sandford Borins

As Professor of Strategic Management at the University of Toronto, Sandford Borins brings InterGovWorld.com readers exclusive insights into how and why the public sector is changing. You'll find new perspectives and questions, observations and objectives, lessons and answers. Cover to Cover, the blog by Prof. Sandford Borins, appears every Thursday.

Inside Cover to Cover

Unified Communications
Data Defence

Unity is a word often heard in the public sector, with myriad agencies and departments looking to foster collective thinking around some of today's most pressing issues. The word, however, doesn't usually get mentioned in the same breath as technology. That's a situation, though, that might soon be changing, thanks to a new software platform known as unified communications.

Inside the latest issue of CGR

More Resources
Driving innovation through effective service management
This white paper discusses how a service-oriented governance framework can help ensure that IT decisions are consistent with business vision, values and strategies-and that IT delivers maximum value to the business. Complimentary with registration.
IT Service Management Solutions and the service desk
This white paper presents the capabilities of IBM Tivoli CCMDB, and describes how Tivoli CCMDB extends the value of the service desk and integrates other essential ITIL processes in support of IBM Service Management. Complimentary with registration.
Info-Tech Research Note: WAN Optimization Tools worth the investment
Multi-site enterprises experiencing WAN bandwidth demand growth and struggling to maintain acceptable application performance should evaluate WAN optimization technology immediately. WAN optimization appliances can dramatically improve inter-site WAN performance, reduce bandwidth requirements, and allow for server centralization. For many enterprises a positive ROI can be achieved in less than a year. Download this research note now. Complimentary with registration.
Advertisement
2007 Salary Calculator
Knowledge Centres at a Glance
White Papers
read more white papers
New blog entries
Thoughts of the day
This week's top stories
Most popular stories of the week
Readers write back
Comments from Intergovworld readers
Government to government
Inside the public sector machine
Government to business
P3: Public-private partnerships
Government to citizen
e-Government service transformation
Blogs
Browse Blogs By:
WiFi Hot Spot Finder
Upload Centre
Upload Your Documents
Contribute and share with your peers by uploading:
- Initiative updates
- White Papers
- Job Links
- Events
- Other
Download Centre
Most popular downloads:
Download More Documents
Download:
- Initiative updates
- White Papers
- Job Links
Subscription Services
Manage your InterGovWorld.com account!
Change your account information, password, e-mail address, and existing e-newsletter subscriptions.
Site Feedback Survey
Tell us what you think of InterGovWorld.com!
FUN SurveyFUN Survey
Take the one-minute Family Unit Networking survey!
IT Salary Survey IT Salary Survey
Take the IT Salary Survey '06 Today
Career Resources
InterGovWorld provides links to resources for government job seekers and current employees, including: current job postings, job search strategies, career options and training, and employee rights, provided by all levels of government from everywhere across Canada.

Public Service Commission of Canada
Service Canada
Jobs in Canada
Service Canada
Public Service Human Resources Management Agency of Canada